17.5 kV Product Information
|
|
|
Mitsubishi Electric Experience
The first generation Bottle was introduced in 1965. Since then, more than 2,424,000 Mitsubishi Vacuum Bottles have been installed world-wide in Mitsubishi Circuit Breakers and more than 100,000 OEM Vacuum Bottles have been sold annually.
Mitsubishi Electric Power Products has 19,725,000 years of Equivalent-Service with0.00018% Bottle failures per year--for every 185,000 Mitsubishi Vacuum Breakers in service, only one will have a bottle fail in a given year.
Features
-
Stainless steel welded-on 10 gauge roof and lifting lugs
-
11 gauge carbon-steel enclosure
-
Two through-wall SST Ground Pads
-
Galvanized legs, two inch increments
-
Three-point breaker door latch
-
37" X 37" footprint
-
MEPPI quality and performance
The Breaker Module
- 17.5kV-1,200A/2,000A, 115kV BIL
- 25kAIC @ X/R=30 (Tested)
- 28kAIC @ANSI X/R=17
- True three cycle operation
- More than 30,000 mechanical operations (tested)
- Twenty 25kA fault interruptions before bottle replacement
- 30 year life design
- One-piece bottle mechanism modle--<1-1/2 hour R&R
- >1000% contact service ability vs. ANSI 800% (tested)
- Axial magnetic field copper-chromium contacts
- Designed and tested to ANSI and IEC Standards
The BH-2 Mechanism
- Simple spring/spring stored energy operation
- One O-CO if motor poweris lost
- <50 moving parts in entire breaker module
- Six second motor charge time
- Universal motor voltages (1.5A running current; 6.9A locked rotor @ 125VDC)
- Single or dual trip coils (<6A current)
- Up to 10a, 10b fixed auxillary contacts
- Greaseless gears utilizing low-friction plating
- Routine maintenance every seven years
DiamondVac Ratings (Tested to ANSI/IEEE and IEC Standards or Higher)
| Breaker Type |
17DV-25-12 or -20 |
Rapid Duty Cycle |
O-0.3s-CO-15sec-CO-50sec-CO |
| Maximum Voltage |
17.5kV |
Opening Time |
30 ms (1.8 cycles) |
| Nominal Voltage |
2.4kV to 17.5kV |
Closing Time |
60 ms (3.6 cycles) |
| Full Load Current |
1,200A or 2,000A |
Minimum Reclosing Time |
50 ms |
| Short Circuit Current |
25kA Interrupting, X/R=30 28kAIC, X/R=17 (per ANSI) |
Range of Reclosing Time |
3-120 cycles |
|
Interrupting Time |
True 3 cycles |
Back-to-Back Capacitor Switching |
500A |
| Frequency |
60Hz |
Reactor Switching |
1,600A (Tested per IEC standards) |
| Full Wave Withstand |
115kV BIL |
Rated Altitude |
1,600m (5,500 feet) |
| Low Frequency Withstand |
50kV |
Temperature Range (Standard) |
+50 degrees C to -40 degrees C |
| Permissable Trip Delay |
2 seconds |
Min. Temperature w/ Extra Heater |
-50 degrees C |
| Close and Latch Capabilities |
25kA RMS, 65kA Crest |
Seismic Level |
IEEE 693 (1997) highest level |
| |
|
|
|
|